Previous PageTable Of Contents

Appendix C - 25x86 Logic Processor Wiring Codes

Industry Standards

Table C-1 lists the wiring codes required to satisfy safety specifications.

Table C-1 Industry Standard Wire Codes

 

Function

Color

Abr.

AWG (min.)

120V AC Input

neutral
line (hot)
ground
ground

white
black
green
green/yellow

WHT
BLK
GRN
GRN/YEL

14
14
14
14

Green or green with yellow stripe must be used only for non current-carrying ground.

HSQ Standards

Table C-2 lists the wiring codes used in production, fieldwork and testing.

Table C-2 HSQ Standard Wire Codes

 

Function

Color

Abr.

AWG (min)

DC Power

+24 Vdc
24 V return (common)
+5 Vdc
5 V return (signal common)

red
black
orange
tan

RED
BLK
ORN
TAN

18
18
18
18

Operations Monitor

Relay, normally. closed
Relay, normally open

blue
purple

BLU
PUR

18
18

Power Control

AC OK status
Battery off command

brown
gray

BRN
GRY

18
18

Maximum Current Capacities

Table C-3 lists the maximum RTU wire current-carrying capacities as specified by the American Wire Gage National Electric Code ANSI/NFPA 70-1987 Articles 310-16, for type THHN (90C) 600V @ 60C [general wiring] and 725-16 & 402-5 for class 1, 2 or 3 remote signaling equipment.

Table C-3 - Wire Capacities

AWG (max.)

Amps

Breaker

18

6

5

16

8

----

14

17.75

15

12

21.3

20

10

28.4

30

8

39

----

© 2000 HSQ Technology

Previous PageTable Of Contents